Description
Used Searle Air Cooled Condenser, model number MVA 244L. The unit is fitted with 8 fans, Copper coils and aluminium fins. Excellent condition. 653KW
|
SI |
MVA244L- N806D |
Total Heat of Rejection |
kW |
653 |
Ambient Temperature |
°C |
35.0 |
Condensing Temperature |
°C |
50.0 |
Actual TD |
K |
15.0 |
Dew or Mid Point |
|
Dew Point |
Refrigerant |
|
R404A |
Hot Gas Inlet Temperature |
°C |
75.0 |
|
|
|
Maximum Allowable Pressure |
bar |
32 |
Maximum Medium Temperature |
°C |
120 |
PED Category |
|
To be confirmed |
|
|
|
Sound Pressure Level |
dB(A) |
58 @ 10 m |
Mean Sound Pressure Level |
dB(A) |
60 @ 10 m |
Sound Power Level |
dB(A) |
92 |
Sound Spectrum 125 Hz |
dB |
95 |
Sound Spectrum 250 Hz |
dB |
92 |
Sound Spectrum 500 Hz |
dB |
88 |
Sound Spectrum 1 kHz |
dB |
89 |
Sound Spectrum 2 kHz |
dB |
84 |
Sound Spectrum 4 kHz |
dB |
77 |
Sound Spectrum 8 kHz |
dB |
71 |
|
|
|
Tube/Fin Material |
|
CU/AL |
Surface Area |
m2 |
1590 |
Subcooling Section |
|
No |
Degrees of Subcooling |
K |
|
Connections |
|
Same End |
Inlet Connection Size |
OD |
4 x 2-5/8″ |
Outlet Connection Size |
OD |
4 x 1-3/8″ |
Subcooling Connections |
|
|
Subcooling Inlet Connection |
OD |
|
Subcooling Outlet Connection |
OD |
|
Orientation |
|
V-Bank |
Air Discharge Direction |
|
Vertical |
Refrigerant Charge |
kg |
99 |
|
|
|
Altitude |
m |
0 |
Air Volume |
m3/s |
46 |
Internal Volume |
dm3 |
301 |
Input Power (Total) |
kW |
12.5 |
Energy Rating |
|
C |
Fan Speed |
1/min |
920 |
Control Voltage (for EC fans) |
V |
0 |
Electrical Supply |
|
400-3-50 |
Rows of Fans |
|
2 |
Fans per Row |
|
4 |
Starting Current (per fan) |
A |
14 |
Full Load Current (per fan) |
A |
4.2 |
|
|
|
Overall Length |
mm |
5098 |
Overall Width |
mm |
2250 |
Overall Height |
mm |
2449 |
Dry Weight |
kg |
1918 |