Telephone: 07885 707111

Shop

60kw air cooled condenser

Category: Tag:

Description

Searle Condenser

SI MDG50- 12S
Total Heat of Rejection kW 60.0
Ambient Temperature °C 30.0
Condensing Temperature °C 44.2
Actual TD K 14.2
Dew or Mid Point Dew Point
Refrigerant R404A
Hot Gas Inlet Temperature °C 70.0
Maximum Allowable Pressure bar 32
Maximum Medium Temperature °C 120
PED Category To be confirmed
Sound Pressure Level dB(A) 33 @ 10 m
Mean Sound Pressure Level dB(A) 36 @ 10 m
Sound Power Level dB(A)
Sound Spectrum 125 Hz dB 36
Sound Spectrum 250 Hz dB 33
Sound Spectrum 500 Hz dB 29
Sound Spectrum 1 kHz dB 29
Sound Spectrum 2 kHz dB 24
Sound Spectrum 4 kHz dB 18
Sound Spectrum 8 kHz dB 7
Tube/Fin Material CU/AL
Surface Area m2 161
Subcooling Section No
Degrees of Subcooling K
Connections Same End
Inlet Connection Size OD 2 1/8″
Outlet Connection Size OD 1 1/8″
Subcooling Connections
Subcooling Inlet Connection OD
Subcooling Outlet Connection OD
Orientation Horizontal
Air Discharge Direction Vertical
Refrigerant Charge kg 13
Altitude m 0
Air Volume m3/s 4.8
Internal Volume dm3 40
Input Power (Total) kW 0.940
Energy Rating C
Fan Speed 1/min 335
Control Voltage (for EC fans) V 0
Electrical Supply 400-3-50
Rows of Fans 1
Fans per Row 2
Starting Current (per fan) A 1.4
Full Load Current (per fan) A 1.2
Overall Length mm 2708
Overall Width mm 1158
Overall Height mm 1225
Dry Weight kg 326
Part Number MDG50-12SAL
Software Release 3.9.7